UTILIZATION CATEGORIES (TYPES) FOR FUSE-LINKS

IEC60269 and EN60269 standards comprise several utilization categories for fuse-links.

Designation of these categories are formed by two parts, first letter states the breaking range of fuse-link:

g

” Full range: Protection against overload and short-circuit.

a

” Partial range: Protection only against short-circuit.

OVERLOAD

This situation is produced when the current is slightly higher

than the “normal” current.

A typical case is when in a house we connect too much

electric devices (heaters, washing machine, dryer, etc) and

then protection operates due to the power

overload

.

SHORT-CIRCUIT

Occurs when the current is much higher than the normal

current (hundreds or thousands times higher).

This defect is produced when there is a contact between two

active parts of different potential that in normal condition

should be isolated.

Typical case could be when two conductors have a damage

in the insulation and there is a contact between them,

producing a

short-circuit

.

Second part of designation state the application of this type of fuse-link:

“G” General use

“M” Motors (or similar loads)

“R” Semiconductor protection (optimized for low I

2

t values)

“S” Semiconductor protection (optimized for low power loss)

“TR” Protection of low voltage side in distribution transformers

“PV” Photovoltaic systems

“B” Mining installations

Combining two parts, we get several categories:

Example:

gG

Protection against overload and short-circuit, general use.

aM

Protection against short-circuit in motor circuits.

aR

Protection against short-circuit for semiconductors

gR

Protection against overload and short-circuit for semiconductors (low I

2

t)

gS

Protection against overload and short-circuit for semiconductors (low power loss)

gPV

Protection against overload and short-circuit for photovoltaic systems

gTR

Protection against overload and short-circuit for distribution transformers

gB

Protection against overload and short-circuit for mining installations

Some time ago there were others types for general use (

gL

,

gF

,

gI, gII

) that have been replaced by

gG

.

gG

Breaking range:

“g”

Protection against

overload and short-circuit.

Application:

“G”

General use

מידע טכני לאופיינים של נתיכים

נתיך סכין אולטרה רפיד כולל דיודה

200KA

כושר ניתוק עד

690V

מתח עבודה

gS

אופיין

נתיכים ובתי נתיך

106685

106695

106690

CE, IEC, UL, ROHS,ISO :

תקנים

In the past, there were other types for general use

gL, gF, gl, gll

which replaced by

gG

.

NH1

NH1

NH1

NH1

NH1

NH2

NH2

NH2

NH2

NH2

NH3

NH3

NH3

NH3

NH3

106685

106686

106687

106688

106689

106690

106691

106692

106693

106694

106695

106696

106697

106698

106699

125A

160A

200A

250A

280A

250A

315A

355A

400A

450A

355A

400A

450A

500A

630A

106683

NH000

NH000

NH000

NH000

NH000

NH000

NH000

NH000

NH00

NH00

106675

106676

106677

106678

106679

106680

106681

106682

106683

106684

מק"ט

תיאור המוצר

20A

25A

32A

40A

50A

63A

80A

100A

125A

160A

זרם נומינלי